Nordic Commercial КАНАЛЬНОГО ТИПА серия

EAC CE RoHS inverter-EUR


ОПИСАНИЕ:

  • Компактные габариты;
  • Малошумный вентилятор;
  • Долговечный моющийся фильтр;
  • Самодиагностика нарушений работы основных блоков и режимов;
  • Защита от неправильного подключения электропитания;
  • Длина трубопровода до 50 м. (для моделей большой мощности).
Auto restart R410A Self diagnosis Self diagnosis error protection24hr Timer mode Super-silent Intelligent-defrost-function Multi-speed-fan Sleep Сooling Dehumidification Heating

МОДЕЛЬНЫЙ РЯД:

CH-ID09NK4 / CH-IU09NK4

Model

CH-ID09NK4 / CH-IU09NK4

Capacity

ColdWarm

kW

2.7/2.9

Electric power supply

~220-240V/50Hz/1Ph

Rated input

ColdWarm

kW

0.84/0.8

Input rate

Cold

А

3.9

Input rate

Warm

3.7

Energy performance

Cold/Warm

EER/ COP

3.21/3.61

Air capability

Indoor unit

m3/h

650

Nominal pressure

Indoor unit

Ра

25

Pressure level

Indoor unit

Ра

0-30

Sound-pressure level

Indoor unit

outdoor unit

dB(A)

36/34/28/26

52

Type of refrigerant coolant

R410A

Refrigerant coolant

kg

1.2

Dimension (width/height/ depth)

Indoor unit/ outdoor unit

mm

925x665x250/

848x320x540

Weight

Indoor unit/ outdoor unit

kg

27/34

Operational temperature range

Cold

°C

-15/+48

Operational temperature range

Warm

°C

-20/+24

Liquid pipeline diameter

mm/inch

6.35/ 1/4’’

Gas pipeline diameter

mm/inch

9.53/ 3/8’’

Maximum pipeline level difference

m

15

Pipeline maximum length

m

20

Quantity of interblock strands (for control)

2*0.75 – up to 20 m long

Main power supply arrea

outdoor.

Quantity of the strands
(powersupply outdoor/indoor)

3(1.0 mm)/

Quantity of the strands
(powersupply outdoor/indoor)

3(1.5 mm)

Factory Freon fill (per the number of running meters)

m.

5

Volumeoffreon.

grаmm/m.p.

30

SEER/SCOP

5.6/3.8

CH-ID12NK4 / CH-IU12NK4

Model

CH-ID12NK4 / CH-IU12NK4

Capacity

ColdWarm

kW

3.50/3.80

Electric power supply

~220-240V/50Hz/1Ph

Rated input

ColdWarm

kW

1.17/1.05

Input rate

Cold

А

5.40

Input rate

Warm

4.90

Energy performance

Cold/Warm

EER/ COP

3.0/3.61

Air capability

Indoor unit

m3/h

750

Nominal pressure

Indoor unit

Ра

25

Pressure level

Indoor unit

Ра

0-35

Sound-pressure level

Indoor unit

outdoor unit

dB(A)

37/36/34/28

52

Type of refrigerant coolant

R410A

Refrigerant coolant

kg

1.2

Dimension (width/height/ depth)

Indoor unit/ outdoor unit

mm

1037х721х266/

848х320х540

Weight

Indoor unit/ outdoor unit

kg

33/34

Operational temperature range

Cold

°C

-15/+48

Operational temperature range

Warm

°C

-20/+24

Liquid pipeline diameter

mm/inch

6.35/ 1/4’’

Gas pipeline diameter

mm/inch

9.53/ 3/8’’

Maximum pipeline level difference

m

15

Pipeline maximum length

m

20

Quantity of interblock strands (for control)

2*0.75 – up to 20 m long

Main power supply arrea

outdoor

Quantity of the strands
(powersupply outdoor/indoor)

3(1.0 mm)/

Quantity of the strands
(powersupply outdoor/indoor)

3(1.5 mm)

Factory Freon fill (per the number of running meters)

m.

5

Volumeoffreon.

grаmm/m.p.

30

SEER/SCOP

5.6/4.0

CH-ID18NK4 / CH-IU18NK4

Model

CH-ID18NK4 / CH-IU18NK4

Capacity

ColdWarm

kW

5.0/5.6

Electric power supply

~220-240V/50Hz/1Ph

Rated input

ColdWarm

kW

1.55/1.55

Input rate

Cold

А

7.50

Input rate

Warm

7.40

Energy performance

Cold/Warm

EER/ COP

3.23/3.61

Air capability

Indoor unit

m3/h

1000

Nominal pressure

Indoor unit

Ра

25

Pressure level

Indoor unit

Ра

0-35

Sound-pressure level

Indoor unit

outdoor unit

dB(A)

40/39/36/28

56

Type of refrigerant coolant

R410A

Refrigerant coolant

kg

1.4

Dimension (width/height/ depth)

Indoor unit/ outdoor unit

mm

1037х721х266/

955х396х700

Weight

Indoor unit/ outdoor unit

kg

33/47

Operational temperature range

Cold

°C

-15/+48

Operational temperature range

Warm

°C

-20/+24

Liquid pipeline diameter

mm/inch

6.35/ 1/4’’

Gas pipeline diameter

mm/inch

12.70/ 1/2’’

Maximum pipeline level difference

m

15

Pipeline maximum length

m

20

Quantity of interblock strands (for control)

2*0.75 – up to 20 m long

Main power supply arrea

outdoor

Quantity of the strands
(powersupply outdoor/indoor)

3(1.0 mm)/

Quantity of the strands
(powersupply outdoor/indoor)

3(2.5 mm)

Factory Freon fill (per the number of running meters)

m.

5

Volumeoffreon.

grаmm/m.p.

30

SEER/SCOP

5.6/3.8

CH-ID24NK4 / CH-IU24NK4

Model

CH-ID24NK4 / CH-IU24NK4

Capacity

ColdWarm

kW

7.00/8.00

Electric power supply

~220-240V/50Hz/1Ph

Rated input

ColdWarm

kW

2.18/2.21

Input rate

Cold

А

10.10

Input rate

Warm

10.20

Energy performance

Cold/Warm

EER/ COP

3.21/3.62

Air capability

Indoor unit

m3/h

1400

Nominal pressure

Indoor unit

Ра

25

Pressure level

Indoor unit

Ра

0-75

Sound-pressure level

Indoor unit

outdoor unit

dB(A)

47/46/44/40

57

Type of refrigerant coolant

R410A

Refrigerant coolant

kg

2.2

Dimension (width/height/ depth)

Indoor unit/ outdoor unit

mm

1279х558х268/

980х427х790

Weight

Indoor unit/ outdoor unit

kg

34/67

Operational temperature range

Cold

°C

-15/+48

Operational temperature range

Warm

°C

-20/+24

Liquid pipeline diameter

mm/inch

9.53/ 3/8’’

Gas pipeline diameter

mm/inch

15.88/ 5/8’’

Maximum pipeline level difference

m

15

Pipeline maximum length

m

30

Quantity of interblock strands (for control)

2*0.75 – up to 20 m long

Main power supply arrea

outdoor

Quantity of the strands
(powersupply outdoor/indoor)

3(1.0 mm)/

Quantity of the strands
(powersupply outdoor/indoor)

3(2.5 mm)

Factory Freon fill (per the number of running meters)

m.

5

Volumeoffreon.

grаmm/m.p.

60

SEER/SCOP

6.1/4.0

CH-ID30NK4 / CH-IU30NK4

Model

CH-ID30NK4 / CH-IU30NK4

Capacity

ColdWarm

kW

8.3/9.2

Electric power supply

~220-240V/50Hz/1Ph

Rated input

ColdWarm

kW

2.67/2.57

Input rate

Cold

А

12.4

Input rate

Warm

12.0

Energy performance

Cold/Warm

EER/ COP

3.11/3.58

Air capability

Indoor unit

m3/h

1400

Nominal pressure

Indoor unit

Ра

37

Pressure level

Indoor unit

Ра

0-75

Sound-pressure level

Indoor unit

outdoor unit

dB(A)

47/46/44/40

58

Type of refrigerant coolant

R410A

Refrigerant coolant

kg

2.4

Dimension (width/height/ depth)

Indoor unit/ outdoor unit

mm

1279х558х268/

980х427х790

Weight

Indoor unit/ outdoor unit

kg

34/71

Operational temperature range

Cold

°C

-15/+48

Operational temperature range

Warm

°C

-20/+24

Liquid pipeline diameter

mm/inch

9.53/ 3/8’’

Gas pipeline diameter

mm/inch

15.88/ 5/8’’

Maximum pipeline level difference

m

15

Pipeline maximum length

m

30

Quantity of interblock strands (for control)

2*1.0 – if longer than 20 m

Main power supply arrea

outdoor

Quantity of the strands
(powersupply outdoor/indoor)

3(1.0 mm)/

Quantity of the strands
(powersupply outdoor/indoor)

3(2.5 mm)

Factory Freon fill (per the number of running meters)

m.

5

Volumeoffreon.

grаmm/m.p.

60

SEER/SCOP

6.1/4.0

CH-ID36NK4/ CH-IU36NM4

Model

CH-ID36NK4/ CH-IU36NM4

Capacity

ColdWarm

kW

10.00/12.00

Electric power supply

~380-415V/50РHz/3Ph

Rated input

ColdWarm

kW

3.12/3.32

Input rate

Cold

А

5.40

Input rate

Warm

А

5.80

Energy performance

Cold/Warm

EER/ COP

3.21/3.61

Air capability

Indoor unit

m3/h

2100

Nominal pressure

Indoor unit

Ра

37

Pressure level

Indoor unit

Ра

0-100

Sound-pressure level

Indoor unit

outdoor unit

dB(A)

53/52/48/44

63

Type of refrigerant coolant

R410A

Refrigerant coolant

kg

3.5

Dimension (width/height/ depth)

Indoor unit/ outdoor unit

mm

1226х775х290/

1107х440х1100

Weight

Indoor unit/ outdoor unit

kg

46/98

Operational temperature range

Cold

°C

-15/+48

Operational temperature range

Warm

°C

-20/+24

Liquid pipeline diameter

mm/inch

9.53/ 3/8’’

Gas pipeline diameter

mm/inch

15.88/ 5/8’’

Maximum pipeline level difference

m

15

Pipeline maximum length

m

30

Quantity of interblock strands (for control)

2*1.0 – if longer than 20 m

Main power supply arrea

outdoor

Quantity of the strands
(powersupply outdoor/indoor)

3(1.0 mm)/

Quantity of the strands
(powersupply outdoor/indoor)

5(1.5 mm)

Factory Freon fill
(per the number of running meters)

m.

5

Volumeoffreon.

grаmm/m.p.

60

SEER/SCOP

5.1/4.0

CH-ID42NK4/ CH-IU42NM4

Model

CH-ID42NK4/ CH-IU42NM4

Capacity

ColdWarm

kW

11.50/13.50

Electric power supply

~380-415V/50РHz/3Ph

Rated input

ColdWarm

kW

4.0/3.9

Input rate

Cold

А

6.90

Input rate

Warm

А

6.70

Energy performance

Cold/Warm

EER/ COP

2.88/3.46

Air capability

Indoor unit

m3/h

2100

Nominal pressure

Indoor unit

Ра

37

Pressure level

Indoor unit

Ра

0-100

Sound-pressure level

Indoor unit

outdoor unit

dB(A)

53/52/48/44

61

Type of refrigerant coolant

R410A

Refrigerant coolant

kg

3.7

Dimension (width/height/ depth)

Indoor unit/ outdoor unit

mm

1226х775х290/

958х412х1349

Weight

Indoor unit/ outdoor unit

kg

46/108

Operational temperature range

Cold

°C

-15/+48

Operational temperature range

Warm

°C

-20/+24

Liquid pipeline diameter

mm/inch

9.53/ 3/8’’

Gas pipeline diameter

mm/inch

15.88/ 5/8’’

Maximum pipeline level difference

m

30

Pipeline maximum length

m

50

Quantity of interblock strands (for control)

2*1.0 – if longer than 20 m

Main power supply arrea

outdoor

Quantity of the strands
(powersupply outdoor/indoor)

3(1.0 mm)/

Quantity of the strands
(powersupply outdoor/indoor)

5(2.5 mm)

Factory Freon fill
(per the number of running meters)

m.

5

Volumeoffreon.

grаmm/m.p.

60

SEER/SCOP

5.6/4.0

CH-ID48NK4/ CH-IU48NM4

Model

CH-ID48NK4/ CH-IU48NM4

Capacity

ColdWarm

kW

14.00/15.50

Electric power supply

~380-415V/50РHz/3Ph

Rated input

ColdWarm

kW

5.1/4.5

Input rate

Cold

А

8.80

Input rate

Warm

А

7.80

Energy performance

Cold/Warm

EER/ COP

2.75/3.44

Air capability

Indoor unit

m3/h

2400

Nominal pressure

Indoor unit

Ра

50

Pressure level

Indoor unit

Ра

0-125

Sound-pressure level

Indoor unit

outdoor unit

dB(A)

55/53/49/45

59

Type of refrigerant coolant

R410A

Refrigerant coolant

kg

4.0

Dimension (width/height/ depth)

Indoor unit/ outdoor unit

mm

1340х750х350/

958х412х1349

Weight

Indoor unit/ outdoor unit

kg

56/114

Operational temperature range

Cold

°C

-15/+48

Operational temperature range

Warm

°C

-20/+24

Liquid pipeline diameter

mm/inch

9.53/ 3/8’’

Gas pipeline diameter

mm/inch

15.88/ 5/8’’

Maximum pipeline level difference

m

30

Pipeline maximum length

m

50

Quantity of interblock strands (for control)

2*1.0 – if longer than 20 m

Main power supply arrea

outdoor

Quantity of the strands
(powersupply outdoor/indoor)

3(1.0 mm)/

Quantity of the strands
(powersupply outdoor/indoor)

5(2.5 mm)

Factory Freon fill
(per the number of running meters)

m.

7.5

Volumeoffreon.

grаmm/m.p.

60

SEER/SCOP

5.6/3.8

CH-ID60NK4/ CH-IU60NM4

Model

CH-ID60NK4/ CH-IU60NM4

Capacity

ColdWarm

kW

16.00/16.50

Electric power supply

~380-415V/50РHz/3Ph

Rated input

ColdWarm

kW

5.6/4.57

Input rate

Cold

А

9.7

Input rate

Warm

А

7.9

Energy performance

Cold/Warm

EER/ COP

2.86/3.61

Air capability

Indoor unit

m3/h

3000

Nominal pressure

Indoor unit

Ра

50

Pressure level

Indoor unit

Ра

0-150

Sound-pressure level

Indoor unit

outdoor unit

dB(A)

57/56/54/49

63

Type of refrigerant coolant

R410A

Refrigerant coolant

kg

5.0

Dimension (width/height/ depth)

Indoor unit/ outdoor unit

mm

1340/750/350

1085/427/1365

Weight

Indoor unit/ outdoor unit

kg

57/126

Operational temperature range

Cold

°C

-15/+48

Operational temperature range

Warm

°C

-20/+24

Liquid pipeline diameter

mm/inch

9.53/ 3/8’’

Gas pipeline diameter

mm/inch

19.05/ 3/4’’

Maximum pipeline level difference

m

30

Pipeline maximum length

m

50

Quantity of interblock strands (for control)

2*1.0 – if longer than 20 m

Main power supply arrea

outdoor

Quantity of the strands
(powersupply outdoor/indoor)

3(1.0 mm)/

Quantity of the strands
(powersupply outdoor/indoor)

5(2.5 mm)

Factory Freon fill
(per the number of running meters)

m.

7.5

Volumeoffreon.

grаmm/m.p.

60

SEER/SCOP

5.6/3.8


CH-D18NK2/CH-U18NK2

Moдель

CH-D18NK2/CH-U18NK2

Производительность

холод/тепло

кВт

5.00/5.40

Источник электропитания

~ 220-240V/50Hz/1Ph

Номинальная потребляемая мощность

холод/тепло

кВт

2.00/1.90

Сила тока

холод/тепло

А

9.20/8.20

Энергоэффективность

холод/тепло

EER/COP

2.50/2.84

Воздухопроизводительность

м3

720/660/540/420

Диапазон давлений

вн. блок

Па

0-30

Уровень звукового давления

вн./нар. блок

дБ(А)

36/33/30/29

56

Тип хладагента

R410a

Габаритные размеры (Ш/В/Г)

вн./нар. блок

мм

1015х275х720/

955х700х395

Вес

вн./нар. блок

кг

31/53

Объем хладагента

кг

1.30

Температурный диапазон работы

холод/тепло

°C

-15/+43/-10/+24

Диаметр жидкостной магистрали

мм/дюйм

6.35/1/4″

Диаметр газовой магистрали

мм/дюйм

12.70/1/2″

Максимальный перепад высоты магистрали

м

15

Максимальная длина магистрали

м

15

Расстояние между болтами крепления нар. блока

мм

560

Количество межблочных жил (на управлении)

2*0.75 – при длине до 20 м.

Место подачи осн. питания

наружный

Количество жил
(подача питания внутр./нар.)

вн. блок

3(1.0 мм)/

Количество жил
(подача питания внутр./нар.)

нар.блок

3(4.0 мм)

Заводская заправка фреоном (на кол-во метров погонных)

м.п.

7

Кол-во заправки фреоном на м.п. (превышение, на каждый метр погонный)

грамм/м.п.

15

CH-D24NK2/CH-U24NK2

Moдель

CH-D24NK2/CH-U24NK2

Производительность

холод/тепло

кВт

7.00/7.40

Источник электропитания

~ 220-240V/50Hz/1Ph

Номинальная потребляемая мощность

холод/тепло

кВт

2.50/2.35

Сила тока

холод/тепло

А

12.00/10.50

Энергоэффективность

холод/тепло

EER/COP

2.80/3.23

Воздухопроизводительность

м3

1265/1000/780/660

Диапазон давлений

вн. блок

Па

0-40

Уровень звукового давления

вн./нар. блок

дБ(А)

46/44/42/36

59

Тип хладагента

R410a

Габаритные размеры (Ш/В/Г)

вн./нар. блок

мм

1260х270х555/

955х700х395

Вес

вн./нар. блок

кг

33/61

Объем хладагента

кг

1.50

Температурный диапазон работы

холод/тепло

°C

-15/+43/-10/+24

Диаметр жидкостной магистрали

мм/дюйм

9.53/ 3/8’’

Диаметр газовой магистрали

мм/дюйм

15.88/5/8″

Максимальный перепад высоты магистрали

м

15

Максимальная длина магистрали

м

15

Расстояние между болтами крепления нар. блока

мм

560

Количество межблочных жил (на управлении)

2*0.75 – при длине до 20 м.

Место подачи осн. питания

наружный

Количество жил
(подача питания внутр./нар.)

вн. блок

3(1.0мм)/

Количество жил
(подача питания внутр./нар.)

нар.блок

3(4.0мм)

Заводская заправка фреоном (на кол-во метров погонных)

м.п.

7

Кол-во заправки фреоном на м.п. (превышение, на каждый метр погонный)

грамм/м.п.

60

CH-D36NK2/CH-U36NM2

Moдель

CH-D36NK2/CH-U36NM2

Производительность

холод/тепло

кВт

10.00/11.50

Источник электропитания

~ 380-415V/50Hz/3Ph

Номинальная потребляемая мощность

холод/тепло

кВт

3.60/3.30

Сила тока

холод/тепло

А

7.60/7.20

Энергоэффективность

холод/тепло

EER/COP

2.77/3.48

Воздухопроизводительность

м3

2100/2030/1860/1730

Диапазон давлений

вн. блок

Па

0-75

Уровень звукового давления

вн./нар. блок

дБ(А)

51/48/46/44

60

Тип хладагента

R410a

Габаритные размеры (Ш/В/Г)

вн./нар. блок

мм

1230х290х790/

980х790х425

Вес

вн./нар. блок

кг

46/69

Объем хладагента

кг

2.20

Температурный диапазон работы

холод/тепло

°C

-15/+43/-10/+24

Диаметр жидкостной магистрали

мм/дюйм

9.53/3/8″

Диаметр газовой магистрали

мм/дюйм

19.05 / 3/4’’

Максимальный перепад высоты магистрали

м

15

Максимальная длина магистрали

м

30

Расстояние между болтами крепления нар. блока

мм

610

Количество межблочных жил (на управлении)

2*1.0 – при длине более 20 м.

Место подачи осн. питания

наружный

Количество жил
(подача питания внутр./нар.)

вн. блок

3(1.5мм)/

Количество жил
(подача питания внутр./нар.)

нар.блок

5(2.5мм)

Заводская заправка фреоном (на кол-во метров погонных)

м.п.

7

Кол-во заправки фреоном на м.п. (превышение, на каждый метр погонный)

грамм/м.п.

120

CH-D48NK2/CH-U48NM2

Moдель

CH-D48NK2/CH-U48NM2

Производительность

холод/тепло

кВт

14.00/15.00

Источник электропитания

~ 380-415V/50Hz/3Ph

Номинальная потребляемая мощность

холод/тепло

кВт

5.00/4.70

Сила тока

холод/тепло

А

10.80/10.50

Энергоэффективность

холод/тепло

EER/COP

2.80/3.19

Воздухопроизводительность

м3

2300/2100/1750/1650

Диапазон давлений

вн. блок

Па

0-100

Уровень звукового давления

вн./нар. блок

дБ(А)

55/52/50/48

60

Тип хладагента

R410a

Габаритные размеры (Ш/В/Г)

вн./нар. блок

мм

1230х290х790/

1120х1100х440

Вес

вн./нар. блок

кг

53/103

Объем хладагента

кг

3.70

Температурный диапазон работы

холод/тепло

°C

-15/+43/-10/+24

Диаметр жидкостной магистрали

мм/дюйм

12.70 / 1/2’’

Диаметр газовой магистрали

мм/дюйм

19.05 / 3/4’’

Максимальный перепад высоты магистрали

м

30

Максимальная длина магистрали

м

30

Расстояние между болтами крепления нар. блока

мм

631

Количество межблочных жил (на управлении)

2*1.0 – при длине более 20 м.

Место подачи осн. питания

наружный

Количество жил
(подача питания внутр./нар.)

вн. блок

3(1.5мм)/

Количество жил
(подача питания внутр./нар.)

нар.блок

5(4.0мм)

Заводская заправка фреоном (на кол-во метров погонных)

м.п.

7

Кол-во заправки фреоном на м.п. (превышение, на каждый метр погонный)

грамм/м.п.

120

CH-D60NK2/CH-U60NM2

Moдель

CH-D60NK2/CH-U60NM2

Производительность

холод/тепло

кВт

16.00/18.00

Источник электропитания

~ 380-415V/50Hz/3Ph

Номинальная потребляемая мощность

холод/тепло

кВт

5.60/5.20

Сила тока

холод/тепло

А

11.60/11.40

Энергоэффективность

холод/тепло

EER/COP

2.85/3.46

Воздухопроизводительность

м3

2500/2300/1900/1800

Диапазон давлений

вн. блок

Па

0-100

Уровень звукового давления

вн./нар. блок

дБ(А)

56/52/49/49

61

Тип хладагента

R410a

Габаритные размеры (Ш/В/Г)

вн./нар. блок

мм

1235х330х830/

980х1350х410

Вес

вн./нар. блок

кг

56/118

Объем хладагента

кг

4.10

Температурный диапазон работы

холод/тепло

°C

-15/+43/-10/+24

Диаметр жидкостной магистрали

мм/дюйм

12.70/1/2″

Диаметр газовой магистрали

мм/дюйм

19.05/3/4″

Максимальный перепад высоты магистрали

м

30

Максимальная длина магистрали

м

30

Расстояние между болтами крепления нар. блока

мм

572

Количество межблочных жил (на управлении)

2*1.0 – при длине более 20 м.

Место подачи осн. питания

наружный

Количество жил
(подача питания внутр./нар.)

вн. блок

3(1.5мм)/

Количество жил
(подача питания внутр./нар.)

нар.блок

5(4.0мм)

Заводская заправка фреоном (на кол-во метров погонных)

м.п.

9.5

Кол-во заправки фреоном на м.п. (превышение, на каждый метр погонный)

грамм/м.п.

120

Cooper & Hunter Support

-

Support 24H

Please fill out all required fields